LEAD BATTERY CHARGERS SKB SK6 - 4.5
Use: emergency lamps
Use: emergency lamps
The lead batteries are lead-acid batteries SKB recombination, although calls are sealed. This manufacturing technology allows the battery to effetturare ca. 200/300 cycles at 100% depth of discharge, while at 30% of its capacity reaches 1000 cycles.For proper operation of the battery, you must follow certain requirements.CHARGE: The charge should be charger with constant voltage by following strictly the information on the battery. An incorrect voltage may lead to the immediate deterioration of the battery. It must not be left discharged after his utlizzo, but needs to be charged immediately.DOWNLOAD: it must not be brought, during the discharge phase, to a voltage to infer 5,25Volt for a 6V battery, 10,50Volt for a 12 Volt battery.WARNING: The battery contains sulfuric acid. Care must be taken when it is manipulated. In case of accidental contact with the acid not touch your eyes nor the mouth. Wash immediately with running water. Go to the hospital emergency room.The battery must be disposed of according to current regulations Voltage: 6 VCapacity: 4.5 AhStandard Charge Current: max. 1/3 of the capacityCharging voltage buffer: 6.75 to 6.90 VCyclic charging voltage: 7.35 to 7.50 VDimensions: W x D x H - HT: 70 x 47 x 98 to 104 mmTerminals: ContactWeight: 0.73 Kg
No customer reviews for the moment.